Your shopping bag is empty
SAFETY
+ Long life type prismatic LiFeP04 cells, suitable for energy storage application.
+ Low voltage system, safety for application.
+ Cell certification: UN38.3, ROHS, IEC62619, UL1973.
+ Battery certification: UN38.3, MSDS, CE
DESIGN
+ Standard 19" rack design.
+ Flexible and easily installation, rack or wall mounted.
+ -20 -+ 55 Degree Celcius widely temperature range.
+ DC Breaker - 125A 1P.
+ Maintainance free.
SCALABILITY
+ Parallel support for more energy.
+ Communication compatible with the major inverter manufacturers.
Optional: Heater-200W.
BATTERY MANAGEMENT SYSTEM
+ Independent protection for charge and discharge.
+ SOC, Alarm, Run display and PC software for detailed operation.
+ OVP, LVP, OCP, LTP protection.
+ RS485, CAN communication port for inverter and Link in & out for battery communication.
SPECIFICATION
Nominal Voltage [V]: 51.2
Nominal Capacity [Ah]: 100
Total Energy [Wh]: 5120
Dimension (W*D*H, mm): 442 * 390 * 130.5
Weight [Kg]: 45
Max. Charging Current [A]: 1C 100A
Max. Discharging Current [A]: 1C 100A
Pulse Discharge Current: 150A @2S
Charging Volatge [V]: 55.2 ~ 57.6
End of Discharge Voltage [V]: 44.8 (Backup Application) / 48 (Cycle Application)
Operation Humidity: 0-95% RH (No condensing)
Operating Temperature Range: Standard Product: Charge: 0 ~ +55 degree celcius; Discharge: -20 ~ +55 Degree Celcius
With Operational Heater: Charge/Discharge: -30 ~ +55 degree celcius
Cycle Life: >6000
Designed Calendar Life: 10 Years
Communication interface: For inverter: RS485,CAN
For battery to battery: LINK-IN, LINK-OUT
Protrction: Over voltage, Low voltage, Over current, Over Temperature, Low Temperature, Short Circuit
Parallel Support: Yes, Max. 15 Sets
Series Support: Not supported
Battery Includes:
-Bolts
-Wall & Rack Brackets
-Manual
-Communication Cable
PRODUCT WARRANTY
5 Years Repair Warranty
Warranties:
All inverters and batteries must be installed by a qualified electrical wireman or Master electrician with a valid registration with the Department of Labour. A valid electrical certificate of compliance (COC) must be issued once installed, specific to the installation of the backup or solar system. The installation must be compliant with SANS 10142 and ALL its parts. Any warranty claim submitted without installation photos, a valid COC and proof of a qualified wireman/master electrician installing the unit, can be rejected and will render the warranty claim null at void.